MTT MS3763B Slim Plug-In RTD Differential Temperature Transmitter

The MTT MS3763B Slim Plug-In RTD Differential Temperature Transmitter measures the temperature difference between two Pt100 RTD sensors and converts it into an isolated, standard DC current or voltage output, extending the same differential-measurement concept as the MS3763 with a wider choice of configurable temperature and differential ranges. Where a process needs to monitor heat exchanger performance, cooling approach temperature, or any application built around comparing two temperature points, the MS3763B can be ordered to match the specific band the process operates in rather than being limited to a single fixed range.

Selectable base temperature ranges spanning from sub-zero to 100°C, together with a choice of narrow or wide differential spans, let this transmitter be specified precisely for the application rather than over- or under-scaled for it. Built-in burnout protection drives the output upscale if any RTD lead opens, giving an unambiguous fault indication, while front-accessible trimmers allow zero and span to be fine-tuned on site. Dual isolated outputs are available so the differential reading can be distributed to two separate destinations from a single module.

Sensor Type2-wire RTD Pt 100Ω
Excitation CurrentApprox. 2mA
Lead Wire Resistance50Ω max per wire
Temperature Range Options-20 to 30°C, 0 to 50°C, or 50 to 100°C
Differential Range Options±10°C, ±20°C, 0 to 20°C, or 0 to 50°C
Output TypesConfigurable current (0-20mA, 4-20mA) or voltage (±10V, 0-10V, 0-5V, 1-5V, etc.); single or dual isolated outputs
Output Load750Ω max (single 4-20mA); 550Ω (Output 1) / 350Ω (Output 2) max (dual)
AdjustmentApprox. ±5% of span, zero and span, via front trimmers
Isolation4-way isolation between input, Output 1, Output 2, and power; 100MΩ min. insulation resistance @500V DC; 2000V AC dielectric strength for 1 minute
CMRR100dB min. (500V AC, 50/60Hz)
Burnout ProtectionUpscale if any of the three wires (RTD A, RTD B, COM) opens
Power Supply100-240V AC (85-264V, 47-63Hz), 24V DC ±10%, or 100-240V DC (85-264V); single output 5.5VA max (AC) / 1.5W max (24V DC) / 6.0W max (DC); dual output 6.5VA max (AC) / 1.8W max (24V DC) / 7.2W max (DC); 160mA fuse standard
AccuracyBetter than ±1.0% of span for most configurations, ±0.5% of span for 0-50°C differences; ±0.2% of span per 10°C temperature effect
Response Time300ms max (0-90%, step input at 100%)
DimensionsW29 x H86 x D125mm (including mounting hardware)
Weight120g (main unit) / 80g (socket) max
TerminalsM3.5 screw terminal with power cover and drop-proof screws, 0.8-1.0 Nm torque
MountingWall or DIN rail mount
Operating Conditions-5 to 55°C, 5-90% RH non-condensing
Storage Temperature-10 to 60°C

Download MTT MS3763B Slim Plug-In RTD Differential Temperature Transmitter information here

Datasheet: MTT_SpecSheet1_MS3763B_Rev120_E