The MTT MS3701F is a slim, plug-in thermocouple temperature transmitter that converts input signals from a thermocouple into commonly used DC signals and provides isolated single or dual output. This model features a fast response time of 500μs (0-90% response).
| Specifications | |||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ● POWER SECTION | |||||||||||||||||||||||||||||||||||||||||||||||||||
| Power Requirements | 100 to 240V AC: 85 to 264V AC (47 to 63Hz) 24V DC: 24V DC±10% 100 to 240V DC: 85 to 264V DC | ||||||||||||||||||||||||||||||||||||||||||||||||||
| Power Sensitivity | Better than ±0.1% of span for each power supply range. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| Power Line Fuse | 160mA fuse is installed (standard). | ||||||||||||||||||||||||||||||||||||||||||||||||||
| Power Consumption |
| ||||||||||||||||||||||||||||||||||||||||||||||||||
| ● INPUT SECTION | |||||||||||||||||||||||||||||||||||||||||||||||||||
| Input Resistance | With or without power: 1MΩ min. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| Allowable Signal Source Resistance | 1kΩ max. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| Input Voltage | 30V DC max., continuous. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| Cold Junction Compensation | A built-in cold junction compensation sensor is used. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| Cold Junction Compensation Error | ±0.5°C max. (25°C±15°C) | ||||||||||||||||||||||||||||||||||||||||||||||||||
| Linearizer | Built-in analog linearizer (6 segments maximum) | ||||||||||||||||||||||||||||||||||||||||||||||||||
| Ranges Available | <Standard specifications> (Temp at 0% input = 0°C)
<Quasi-standard specifications>
Input Spec Ex. 1: For K -100 to 400°C, the input span is 500°C and the bias -0.2x the input span. Input Spec Ex. 2: For J 300 to 400°C, the input span is 100°C and the bias 3x the input span. Note 1: Input span: 4mV min. Note 2: For input temperature ranges starting from any specified temperature below 0°C, the accuracy may be partly out of specification. Note 3: For the type B thermocouple, the accuracy in the temperature range below 600°C is not guaranteed. Note 4: Any specification out of the temperature range or bias requirement listed above is handled as a special order. | ||||||||||||||||||||||||||||||||||||||||||||||||||
| ● OUTPUT SECTION | |||||||||||||||||||||||||||||||||||||||||||||||||||
| Allowable Output Load |
| ||||||||||||||||||||||||||||||||||||||||||||||||||
Download MTT MS3701F Slim Plug-In Thermocouple Temperature Transmitter information here
Datasheet: MTT_SpecSheet1_MS3701F_Rev140_E
Manual: