WhatsApp Us -- Email Us

Instrumentation Calculators & Unit Converters

Six free calculators for the numbers instrumentation engineers work out every day: pressure and flow unit conversion, turndown ratio, DP level calibration, mag meter velocity and 4–20 mA scaling. Type a value and the result updates instantly. No sign-up, nothing to download.

Free · No sign-up · Results update as you type · Metric and imperial units

01 · Unit Conversion

Pressure Unit Converter

Enter a value in any pressure unit — every equivalent updates live below.


UnitEquivalent value

Need the instrument? Pressure transmitters → Pressure transducers → Pressure gauges →

Show reference formula
All units are converted through a common base of pascals (Pa).
value_Pa = value × factor[from_unit]
result_unit = value_Pa ÷ factor[result_unit]
e.g. 1 bar = 100 000 Pa · 1 psi = 6 894.757 Pa · 1 atm = 101 325 Pa

02 · Unit Conversion

Flow Unit Converter

Volume/mass unit and time unit are picked independently, then converted into every combination at once — not locked to a fixed list of unit+time pairs.


Unit/ second/ minute/ hour/ day

The highlighted cell matches what you entered above. Every other cell is that same flow rate re-expressed in a different unit/time combination — e.g. read the bbl row's / day column for oil bbl/day, or the MMSCF row's / day column for MMSCFD.

Need the instrument? Flow meters → Electromagnetic flow meters → Flow computers →

Show reference formula
Volumetric base: L/s · Mass base: kg/s
value_base/s = value × unit_factor ÷ time_seconds
result_cell = value_base/s ÷ unit_factor[row] × time_seconds[column]
MMSCF uses standard conditions (60°F, 14.696 psia). Converting between volumetric and mass flow requires fluid density — not included here.

03 · Rangeability

Turn-Down Ratio Calculator

Compares the maximum and minimum usable value of a flow meter, control valve, or any rangeable instrument.


12.5 : 1 Q min = 8.0% of Q max

Need the instrument? Vortex flow meters → Ultrasonic flow meters → Thermal mass flow meters →

Show reference formula
Turn-down ratio = Q max ÷ Q min, expressed as X : 1
Higher ratio → instrument holds accuracy over a wider range.

04 · Transmitter Sizing

Differential Pressure Level Calculation

Computes LRV / URV calibration points for a DP level transmitter from tank geometry and specific gravity.

vented to atmosphere SG1 Process fluid — SG1 L h X HP LP → atm (0 ref)

SG1 process fluid · L span between taps · h transmitter offset below lower tap. The upper side is open to atmosphere, so only one process connection is needed.

SG1 Process fluid — SG1 L dry leg — vapor only, no column weight h X HP LP

SG1 process fluid · L span between taps · h transmitter offset below lower tap. The dry leg carries vapor pressure only — its length adds no column weight, so vapor pressure cancels out of the DP.

SG1 Process fluid — SG1 L H SG2 h X HP LP

SG1 process fluid · SG2 wet-leg fill fluid · L span between taps · h transmitter offset below lower tap · H wet leg height, transmitter to upper tap. HP = process (dry, short leg) · LP = reference (wet, filled leg).


LRV — 0% level0.00kPa
URV — 100% level0.00kPa

Go deeper: DP level calculation guide → Need the instrument? Level transmitters → Pressure transmitters →

Show reference formula

05 · Mag Meter Sizing

Velocity ↔ Flow Rate Converter

Converts between line velocity and volumetric flow rate for a given pipe internal diameter — sized for electromagnetic flow meters.

m/s

0.00 m³/h Flow rate

Need the instrument? Electromagnetic flow meters → All flow meters →

Show reference formula
Pipe area: A = π ÷ 4 × D²
Flow rate: Q = V × A
Velocity: V = Q ÷ A
Electromagnetic flow meters typically need 0.3–10 m/s line velocity for a reliable, low-noise signal — outside that band, accuracy and repeatability degrade even though the meter still reads.

06 · Signal Scaling

PV ↔ mA Converter

Convert between a process value and its transmitted analog signal using the calibrated range.

°C

12.00 mA 50.0% of range

Need the instrument? Signal conditioners → Signal isolators → Process indicators →

Show reference formula
% = (PV − LRV) ÷ (URV − LRV)
Signal = Signal_lo + % × (Signal_hi − Signal_lo)
(Signal → PV runs the same equations in reverse.)

Need the instrument, not just the number?

Tell us your range, medium and process connection and we will recommend the right transmitter or meter.

⏱ We reply within 1 working day.

Worked examples

See how each calculator works

Pressure Unit Converter

A transmitter is ranged 0–10 bar. Enter 10 bar and read 1,000 kPa, 145.04 psi or 10.197 kgf/cm².

Formula: value in Pa = value × unit factor, then divide by the target unit’s factor.

Flow Unit Converter

A pump is rated 50 m³/h. Pick m³ and per hour, enter 50, and read 833.3 L/min, 13.89 L/s or 220.1 US gpm.

Formula: choose the volume or mass unit and the time unit separately; every combination is shown at once.

Turndown Ratio Calculator

A flow meter reads from 8 m³/h up to 100 m³/h. Turndown = 100 ÷ 8 = 12.5 : 1, so the lowest usable flow is 8% of the maximum.

Formula: turndown ratio = maximum flow ÷ minimum flow.

DP Level Calculator

Closed tank with a wet leg: SG 1.0, taps 2.0 m apart, transmitter 0.5 m below the lower tap, 2.5 m wet leg of SG 1.0. The calibration is LRV −19.61 kPa, URV 0 kPa.

Formula: LRV = g·(SG1·h − SG2·H), URV = g·(SG1·(h + L) − SG2·H). Full method in our DP level calculation guide.

Velocity ↔ Flow (Mag Meter)

A DN100 line (100 mm bore) running at 2 m/s carries about 56.5 m³/h. Enter the flow instead to see the velocity.

Formula: Q = V × A, where A = π ÷ 4 × D².

PV ↔ mA Converter

A 0–10 bar transmitter on 4–20 mA gives 12 mA at 5 bar. Reading 8 mA means (8 − 4) ÷ 16 × 10 = 2.5 bar.

Formula: mA = 4 + (PV − LRV) ÷ (URV − LRV) × 16.

FAQ

Common questions

How do I convert 4–20 mA to a process value?

Subtract 4 from the current, divide by 16, then multiply by the span and add the lower range value: PV = LRV + (mA − 4) ÷ 16 × (URV − LRV). For a 0–10 bar transmitter reading 12 mA, that is 5 bar.

Why does a 4–20 mA loop start at 4 mA instead of 0?

The 4 mA “live zero” separates a real 0% reading from a broken wire or a dead loop, and it leaves enough current to power a two-wire transmitter. NAMUR NE43 uses signals at or below 3.6 mA and at or above 21 mA to flag a fault.

What is turndown ratio and why does it matter?

Turndown ratio is the maximum flow divided by the minimum flow a meter or control valve can handle within its stated accuracy. A 10 : 1 meter on a 200 m³/h line holds accuracy down to 20 m³/h. Make sure your normal operating flow sits comfortably inside that range, not at its edge.

When should I use a wet leg for DP level measurement?

Use a wet (filled) reference leg when vapour above the liquid can condense, such as steam or humid services, because condensate in a dry leg adds an unpredictable head. A wet leg gives a constant reference pressure but shifts the calibration to a negative LRV, so confirm the transmitter supports zero elevation.

What velocity range does an electromagnetic flow meter need?

Most electromagnetic flow meters are specified from roughly 0.3 m/s up to 10 m/s, with the best performance in the middle of that band. They also need a conductive liquid and a full pipe, so always check the datasheet for the exact limits.

How accurate are these calculators?

They use standard conversion factors and textbook formulas, so they suit estimating, sizing and sanity checks. For calibration and safety-critical work, confirm every value against the instrument datasheet and your plant procedures.

Shopping Cart

Search 3,000+ products

Type a model number, brand or product type.

Popular categories
Can't find it? Tell us what you need. Request a Quote →