MTT MS3705 Slim Plug-In Alarm Setter with Isolated Dual Output

The MS3705 is a high-reliability, slim plug-in alarm setter designed to monitor and safeguard industrial process loops. This precision instrument continuously compares incoming DC current or voltage signals against two independently configured set-points (upper and lower limits), providing isolated dual Form C relay contact closure outputs for dependable alarm interlocking and process trip execution. Engineered to optimize space inside control panels, the module features a compact 29mm wide housing designed for flexible wall or DIN rail mounting. It boasts robust galvanic isolation across all active channels with a 2000V AC dielectric strength rating between the input, power supply, and each individual relay output, effectively halting ground loop propagation and enhancing noise immunity. With field-adjustable rotary switches, operations and maintenance teams can easily calibrate trip parameters to maintain precise, real-time safety thresholds across demanding factory automation architectures.

Key Product Features

  • Dual-Limit Alarm Monitoring: Compares DC current or voltage loop levels against two independent upper and lower set-points to orchestrate safe system trips.
  • Form C Relay Contact Outputs: Features two completely independent, isolated Form C relay contact closures supporting a robust rated load of 5A at 125V AC / 5A at 30V DC.
  • Precise Front-Panel Configuration: Incorporates intuitive, front-accessible rotary switches that allow operators to dial in trip points from 0 to 99% of span in granular 1% incremental steps.
  • Excellent Galvanic Isolation: Full multi-channel isolation barrier rated for 2000V AC dielectric strength for 1 minute, preventing dangerous high-voltage transients from crossing between input, power, and relay lines.
  • Industrial Resilience: Built with a flame-retardant UL 94V-0 rated ABS resin housing, featuring integrated red status LEDs for rapid visual trip indication and a standard premium HumiSeal® polyurethane conformal coating.

<td

Technical Specifications
● POWER SECTION
Power Requirements100 to 240V AC: 85 to 264V AC (47 to 63Hz)
24V DC: 24V DC ±10%
100 to 240V DC: 85 to 264V DC
Power SensitivityBetter than ±0.1% of span for each power supply range.
Power Line Fuse160mA fuse is installed (standard).
Power Consumption
100-240V AC24V DC100-240V DC
6.5VA max2.0W max8.4W max
● INPUT SECTION
Input Configuration OptionsA: 4 to 20mA DC | D: 0 to 20mA DC
3: 0 to 1V DC | 4: 0 to 10V DC | 5: 0 to 5V DC | 6: 1 to 5V DC
Input ResistanceVoltage Input (DC): With power: 1MΩ min. / Without power: 10kΩ min.
Current Input (DC): 4 to 20mA (std.): 250Ω
Allowable Input LimitsVoltage Input Model: 30V DC max., continuous.
Current Input Model: 40mA DC max., continuous.
● OUTPUT SECTION
Output SignalTwo independent Form C relay contact closure signals.
Trip ConfigurationAdjustment Mechanism: Front-accessible rotary switch.
Setting Range: 0 to 99% of span (in steps of 1%).
Accuracy: ±0.5% of span.
Hysteresis: 1.0% ± 0.3% of span.
Relay Trip IndicatorsRed LED status indicator illuminates when relay is activated.
Unpowered State BehaviorCOM and NC are closed for each independent output channel.
Relay Start-up LimitationRelay becomes active and ready for operation approx. 2 seconds after power-up.
● PERFORMANCE
Temperature EffectBetter than ±0.15% of span per 10°C change in ambient temperature.
Response Time150ms max. (0 to 90%) with a step input at 100% (Standard).
Optional fast-response code (/K) provides 100ms max.
Galvanic IsolationComplete multi-way isolation between input, output 1, output 2, power, and ground channels.
Insulation Resistance100MΩ min. (@500V DC) across input, output 1, output 2, power, and ground paths.
Dielectric StrengthInput / Output 1 / Output 2 / [Power, Ground]: 2000V AC for 1 minute (Cutoff current: 0.5mA)
Power / Ground: 2000V AC for 1 minute (Cutoff current: 5.0mA)
Relay Contact CapabilityRated Load: 5A at 125V AC, 5A at 30V DC
Maximum Allowable Voltage: 250V AC, 30V DC
Maximum Allowable Current: 5A (Normally Open) / 3A (Normally Closed)
Contact Service LifeElectrical Life (NO): 5A at 250V AC: 50×10³ cycles | 5A at 30V DC: 100×10³ cycles (at 1,800 cycles/h)
Mechanical Life: 5×10⁶ cycles (at 18,000 cycles/h)
Surge Withstand CapabilityTested in strict accordance with ANSI/IEEE C37.90.1-1989.
● PHYSICAL
Mounting ConfigurationSurface wall mounting or standard DIN rail installation.
Wiring ConnectionRobust M3.5 screw terminals (including protective cover & drop-proof structural screws).
Recommended Torque0.8 to 1.0 [Nm] * Recommended assembly torque.
DimensionsW29 × H86 × D125 mm (inclusive of basic socket assembly & hardware).
Product Net WeightMain module housing: 130g max. | Socket base portion: 80g max.
● MATERIAL
Enclosure ShellABS resin (Flame class: UL 94V-0).
Terminal Block CorePBT resin (Flame class: UL 94V-0).