Contrec 515 Heat Calculator (HC06)

The Contrec 515 HC06 Heat Calculator measures the volume, mass, and energy content of fluids in heating and cooling systems, using a single or stacked differential pressure flowmeter with a volumetric span, plus temperature readings from the supply and return lines.

It calculates flow using standard DP equations, taking into account the actual conditions the flowmeter was calibrated under, so the numbers stay accurate as line conditions shift. For water, it works out mass flow and energy using the IAPWS Industrial Formulation (1997); for other fluids, it uses internal enthalpy and density tables.

In actual application, this covers most heating and cooling metering setups already built around a DP flowmeter, so it is a straightforward retrofit onto an existing orifice plate or similar element without changing the flow element itself.

Before we quote this, we would normally check your DP flowmeter’s calibrated span, your supply/return temperature range, and the fluid you are measuring.

Hope this helps.

FunctionHeat Calculator, Differential Pressure Flow Meter (Volumetric Span); measures volume, mass, and energy content of fluids in heating/cooling systems using single or stacked DP volumetric flow inputs plus supply/return temperature; for water, calculates mass flow and energy per IAPWS Industrial Formulation (1997); for other fluids, uses internal enthalpy/density tables
DisplayBacklit LCD, 7-digit numeric (15.5mm) and 11-character alphanumeric (6mm) display, 0.3 second update rate
InputsSingle or stacked DP analogue input (4-20mA/0-5V/1-5V) for volumetric span flow calculation, calibrated to the flowmeter’s own conditions; RTD PT100/PT500 (-200 to 350°C) supply and return temperature inputs; up to 4 analogue channels with 20-point non-linear correction
Accuracy0.05% full scale at 20°C; 0.1% typical across full temperature range; RTD 0.1°C typical
Outputs2 x isolated pulse (200mA/30Vdc) or 4-20mA outputs (0.05% accuracy); 2 standard relay outputs (3A max) for alarms, 2 additional optional
Power100-240Vac (50-60Hz) or 12-28V DC, up to 10W; front-panel adjustable 8-24V DC transducer supply
EnclosureIP65 (NEMA 4X) panel mount; conformal coating option extends temperature range
Operating Temperature+5 to +40°C standard; -20 to +60°C with conformal coating
Dimensions147 x 74 x 170mm (W x H x D); panel cut-out 139 x 67mm
CommunicationCOM-1 RS232, COM-2 RS485 or Ethernet (optional); ASCII, Modbus RTU/TCP-IP, and Printer protocols, 2400-19200 baud

Download Contrec 515 Heat Calculator (HC06) information here

Datasheet: 515-HC06-AP

Manual: 515-HC06-OM