Contrec 515 Heat Calculator (HC04)

Heating and cooling systems using differential pressure (DP) meters, orifice plates, or V-Cones need more than just a flow reading to calculate real energy use. You need density, enthalpy, and a few other thermodynamic properties, worked out correctly for the actual fluid temperature. That is what the Contrec 515 HC04 Heat Calculator does.

It reads a single or stacked DP input from the flow element, using the ISO 5167 or V-Cone equations, and combines this with feed and return temperature readings. From actual application, this matters because DP flow calculations shift with fluid density and viscosity, which themselves change with temperature, so getting this right needs to happen inside the instrument, not as a separate manual correction.

The calculations are based on the IAPWS Industrial Formulation (1997), the same reference used for accurate steam and water thermodynamic properties. Temperature readings are used to work out fluid density and specific enthalpy, and the instrument also calculates the isentropic exponent and absolute viscosity needed for the DP flow equations themselves.

Before we quote this, we would normally check your DP transmitter or flow element type, the feed/return temperature range, and whether you need a single or stacked DP configuration.

Hope this helps.

FunctionHeat Calculator for stacked DP (differential pressure) meters, ISO 5167 and V-Cones; measures volume, mass, and energy content of fluids in heating or cooling systems using single or stacked DP flow inputs plus feed/return temperature; calculates fluid density, specific enthalpy, isentropic exponent, and absolute viscosity using the IAPWS Industrial Formulation (1997)
DisplayBacklit LCD, 7-digit numeric (15.5mm) and 11-character alphanumeric (6mm) display, 0.3 second update rate
InputsSingle or stacked differential pressure (DP) analogue inputs (4-20mA/0-5V/1-5V) for ISO 5167 orifice/V-Cone flow calculation; RTD PT100/PT500 (-200 to 350°C) feed and return temperature inputs; up to 4 analogue channels with 20-point non-linear correction
Accuracy0.05% full scale at 20°C; 0.1% typical across full temperature range; RTD 0.1°C typical
Outputs2 x isolated pulse (200mA/30Vdc) or 4-20mA outputs (0.05% accuracy); 2 standard relay outputs (3A max) for alarms, 2 additional optional
Power100-240Vac (50-60Hz) or 12-28V DC, up to 10W; front-panel adjustable 8-24V DC transducer supply
EnclosureIP65 (NEMA 4X) panel mount; conformal coating option extends temperature range
Operating Temperature+5 to +40°C standard; -20 to +60°C with conformal coating
Dimensions147 x 74 x 170mm (W x H x D); panel cut-out 139 x 67mm
CommunicationCOM-1 RS232, COM-2 RS485 or Ethernet (optional); ASCII, Modbus RTU/TCP-IP, and Printer protocols, 2400-19200 baud

Download Contrec 515 Heat Calculator (HC04) information here

Datasheet: 515-HC04-AP

Manual: 515-HC04-OM