Contrec 515 Flow Computer – Liquid & Petroleum Measurement (FC01)

The Contrec 515-FC01 is a rate totaliser for liquid and petroleum flow measurement, built on Contrec’s 515 flow computer platform. It reads a frequency or analogue signal from a volumetric flowmeter and shows flow rate, resettable total, and accumulated total on its display, with the option to correct for a live or fixed density value.

Being on the 515 platform, it shares the same solid hardware base as the rest of the 515 family: multiple analogue and frequency inputs, RS232/RS485 or Ethernet communication with Modbus support, and relay or 4-20mA outputs depending on how it’s configured. This is the more general-purpose application code in the range, so we’d normally check whether one of the more specific 515 applications, like the natural gas or steam computers, is actually a better fit before quoting this one.

Before we quote this, we would normally confirm the flowmeter’s output type (frequency or 4-20mA), whether density compensation is needed, and the communication protocol the customer’s system expects. Hope this helps.

FunctionRate totaliser for liquid and petroleum flow measurement, accepts frequency or analogue output from a volumetric flowmeter
DisplayBacklit LCD, 7-digit numeric (15.5mm) and 11-character alphanumeric (6mm) display, 0.3 second update rate
InputsFrequency/pulse (millivolt, reed switch, Namur proximity) or 4-20mA analogue; RTD PT100/PT500 (-200 to 350°C); up to 4 analogue channels with 20-point non-linear correction
Accuracy0.05% full scale at 20°C; 0.1% typical across full temperature range; RTD 0.1°C typical
Outputs2 x isolated pulse (200mA/30Vdc) or 4-20mA outputs (0.05% accuracy); 2 standard relay outputs (3A max), 2 additional optional
Power100-240Vac (50-60Hz) or 12-28V DC, up to 10W; front-panel adjustable 8-24V DC transducer supply
EnclosureIP65 (NEMA 4X) panel mount; conformal coating option extends temperature range
Operating Temperature+5 to +40°C standard; -20 to +60°C with conformal coating
Dimensions147 x 74 x 170mm (W x H x D); panel cut-out 139 x 67mm
CommunicationCOM-1 RS232, COM-2 RS485 or Ethernet (optional); ASCII, Modbus RTU/TCP-IP, and Printer protocols, 2400-19200 baud

Download Contrec 515 Flow Computer – Liquid & Petroleum Measurement (FC01) information here

Datasheet: 515-FC01-AP

Manual: 515-FC01-OM