Setra 264 Low Differential Pressure Transducer

Read more

Ranges: {010WD} 0 to 10.0" W.C.
Output: {11} 4-20 mA
Electrical Termination: {T1} Terminal Strip
Accuracy: {C} +/- 1% FS - no Cal. Cert

Available on backorder

The Setra Model 264 is the global industry standard very low differential pressure transducer engineered for exceptional accuracy, long-term stability, and peace-of-mind reliability in critical HVAC building automation and energy management systems. At the engineering core of this compact instrument is an all-stainless steel, dead-ended welded capacitive sensing element that requires minimal amplification and prevents fluid cross-contamination. Optimized for clean, non-conducting gas media, the Model 264 features a robust structural layout that accommodates standard wall or conduit mounting styles with integrated brass barbed fittings for rapid field installation. Operating on a low-cost, unregulated 9 to 30 VDC power supply, it delivers a highly stable 4-20mA current loop or analog voltage output, providing clean telemetry density for advanced Building Automation Systems (BAS). Backed by an industry-leading 3-year unconditional warranty, the Model 264 eliminates ground loop issues and maintains superior tracking for static pressure, cleanroom, and VAV box control architectures.

Key Product Features

  • All-Stainless Steel Capacitive Sensor: Employs a patented, dead-ended welded capacitive sensor design delivering excellent accuracy and resistance to high overpressure.
  • Low-Cost Power & Simple Telemetry: Operates efficiently on low-cost unregulated 9-30 VDC loop power while outputting simultaneous 4-20mA current or 0-5 VDC voltage configurations.
  • Unconditional 3-Year Warranty: Outfitted with an unconditional 3-year factory warranty guaranteeing peace of mind well past typical initial BAS commissioning phases.
  • Versatile Field Mounting Arrays: Available in both standard base wall mount or conduit cover configurations with accessible zero/span settings for effortless commissioning.
  • High Environmental Resilience: Fire-retardant glass-filled polyester enclosure rated to UL 94V-0 standards preserves high performance across a wide operating temperature envelope.
Setra Model 264 Technical Specifications
● POWER SECTION
Supply Voltage Requirements4 to 20 mA Output: 9 to 30 VDC (Minimum VDC = 9 + 0.02 x resistance of receiver plus line)
0 to 5 VDC Output: 9 to 30 VDC
0 to 10 VDC Output: 12 to 30 VDC
External Load LimitsCurrent Loop: 0 to 800 ohms
Voltage Outputs: Calibrated into a 50k ohm load; operable into 5000 ohms or greater
● INPUT SECTION
Pressure Ranges AvailableUnidirectional: 0 to 0.1 in. WC up to 0 to 100 in. WC
Bidirectional: ±0.05 in. WC up to ±50 in. WC
Pressure Media CompatibilityAir or similar non-conducting gases.
Maximum Overpressure LimitsRanges ≤ 10 in. WC: 10 psi (Proof), 15 psi (Burst)
Ranges > 10 in. WC: 30 psi (Proof), 45 psi (Burst)
● OUTPUT SECTION
Output Signal Configurations4 to 20 mA DC (2-wire loop)
0 to 5 VDC (3-wire configuration)
0 to 10 VDC (3-wire configuration)
Bidirectional Output Center2.5 VDC or 12 mA at zero differential pressure.
Output Calibration ToleranceZero Signal: ±50 mV standard (±0.16 mA for current outputs)
Full Scale Span: ±50 mV standard (±0.16 mA for current outputs)
● PERFORMANCE
Accuracy (at 70°F / 21°C)±1.0% FS standard (Optional premium tiers: ±0.4% FS or ±0.25% FS)
*Includes Root Sum Square (RSS) of Non-Linearity, Hysteresis, and Non-Repeatability.
Long-Term Stability±0.5% FS maximum shift per year.
Thermal Coefficients (0 to 150°F)Zero Shift: ±0.033% FS/°F
Span Shift: ±0.033% FS/°F
Warm-Up & Position EffectsWarm-up time: 0.1 second to full accuracy specifications.
Factory calibrated at 0g in the vertical plane (Position shift varies from 2.3% FS/g at 0.1 in. WC down to 0.15% FS/g at 10 in. WC).
● PHYSICAL
Enclosure Shell MaterialFire-retardant glass-filled polyester resin (Conforms to flammability rating UL 94V-0).
Pressure Ports / FittingsStandard 3/16″ O.D. brass barbed fittings (optimized for 1/4″ push-on vinyl tubing).
Electrical ConnectionsRobust multi-position screw terminal strip (Optional integrated conduit enclosure lid).
Weight ParametersBase module weight: 8.5 ounces (241 grams) continuous mass.
● STANDARDS CONFORMITY
Environmental LimitsOperating Temperature Bounds: 0 to 175°F (-18 to 79°C)

Download Setra 264 Low Differential Pressure Transducer information here

Datasheet: Setra_Model_264_Data_Sheet 
Manual: Setra_Model_264_Manual

You may also like…

Shopping Cart


Do you want to hide this popup?