MTT MS3772 slim plug-in programmable RTD temperature transmitter

MTT MS3772 Slim Plug-In Programmable RTD Temperature Transmitter

SKU: MS3772

A slim plug-in transmitter, PC-programmable via RS-232C for Pt100, JPt100, or Pt50 RTDs, that converts RTD input into an isolated standard DC output.

Category: Signal Conditioners, Signal Isolators

Price on request

Send us your requirement and we'll reply with a quotation and technical advice.

⏱ We reply within 1 working day. Specs & downloads ↓
🛠️
Lifetime technical support
🚚
Free domestic shipping
🎯
Calibration services

Follow Celectric's WhatsApp Channel →

Product details

The MTT MS3772 Slim Plug-In Programmable RTD Temperature Transmitter converts a 3-wire RTD input into a standard isolated DC current or voltage output, supporting Pt100, JPt100, and Pt50 sensor types on a single hardware platform. Rather than stocking a different transmitter for each RTD type and range combination, panel builders can configure one MS3772 to match the sensor and temperature span the application calls for.

Setup is done from a PC over an RS-232C connection, where the RTD type, measuring range, output configuration, and burnout behavior are all programmed digitally, and zero and span are fine-tuned the same way rather than with mechanical trimmers. Selectable burnout protection drives the output upscale or downscale if the RTD lead opens, giving an unambiguous fault indication, while LED status indicators show run and fault conditions at a glance. Four-way isolation between input, both outputs, and power keeps the transmitted temperature signal protected from noise and ground loops.

Input Signal3-wire RTD (JIS standard)
RTD OptionsPt 100Ω (ITS-90/IPTS-68), JPt 100Ω (JIS ’89), Pt 50Ω (JIS ’81)
Temperature Range-200 to 660°C (varies by RTD type)
Excitation CurrentApprox. 1mA
Lead Wire Resistance200Ω max per wire
Minimum Input Span25°C
Input Accuracy0.01-0.02% factor (inversely proportional to span)
Output OptionsSingle: 4-20mA DC, 0-10V DC, 0-5V DC, 1-5V DC; Dual: current/voltage or current/current combinations
Output Load2mA max (voltage); 750Ω max (single 4-20mA)
Adjustment±4% of span, zero and span, configured via RS-232C
Output Accuracy±0.04% max
Burnout ProtectionSelectable upscale, downscale, or none; detection time 10s max
Isolation4-way isolation between input, Output 1, Output 2, power, and ground; 2000V AC dielectric strength for 1 minute
CMRR100dB min. (500V AC, 50/60Hz)
Response Time260ms max (0-90%, step input)
Temperature Effect100ppm/°C max
Power Supply100-240V AC (50-60Hz), 24V DC, or 100-240V DC; single output 5.0VA max (AC) / 1.1W max (24V DC); dual output 5.0VA / 1.5W max
DimensionsW29 x H86 x D125mm
Weight120g (main unit) / 80g (socket) max
TerminalsM3.5 screw terminals, 0.8-1.0 Nm torque, gold-plated contacts
MountingWall or DIN rail mount
Operating Conditions-5 to 55°C, 5-90% RH non-condensing
Storage Temperature-10 to 60°C
Additional FeaturesRS-232C PC configuration; LED status indicators (blue/red)

Frequently Asked Questions

What is the MTT MS3772 used for?
It converts a 3-wire RTD input into a standard isolated DC current or voltage output, with the RTD type, measuring range, and burnout behavior all set through configuration rather than ordered as a fixed model. This lets one hardware platform cover applications that would otherwise need a different transmitter for each RTD type and range.

Which RTD types are supported?
Pt100 (ITS-90/IPTS-68), JPt100 (JIS ’89), and Pt50 (JIS ’81), across a temperature range of -200 to 660°C depending on the RTD type selected. Tell us your RTD type and expected temperature range and we can confirm the configuration.

How is it configured for a specific RTD type and range?
Configuration is done via RS-232C, where the RTD type, measuring range, and output span are all set in software rather than by physical model selection, with zero and span fine-tuned digitally on top of the base configuration.

What happens if the RTD lead opens or breaks?
Burnout protection is selectable: the output drives either full upscale or full downscale on an open RTD lead, so your control system sees an unambiguous fault rather than a signal that drifts and could be mistaken for a real reading.

How do I know if the MS3772 is right for my application?
If you’re measuring with a 3-wire RTD and need an isolated transmitted signal with configurable range and burnout behavior, the MS3772 covers Pt100/JPt100/Pt50 in one slim DIN-rail unit. Send us your RTD type, measuring range, and required output signal and we’ll confirm before you order.

Download MTT MS3772 Slim Plug-In Programmable RTD Temperature Transmitter information here