MTT MS3104 Terminal Block Type High-Level Signal Conditioner (Isolator)

We recently had an enquiry from a customer running a single high-level DC signal — a 4-20mA transmitter output — that needed to feed two separate systems at the same time: one for control, one for a separate alarm or recorder. Splitting a loop like that isn’t as simple as wiring the signal to two inputs. You risk loading down the loop, and if the two downstream systems don’t share a common ground, you can end up with noise or even damage from ground loop currents.

This is where the MTT MS3104 terminal block signal conditioner comes in. It isn’t just a distributor — it’s a signal isolator with two completely independent, isolated DC outputs from a single DC current or voltage input. Full isolation between the input, both outputs, and the power supply means each connected device sees a clean signal, with no shared ground path to pick up noise or carry a fault back into the loop.

In actual application, panel power isn’t always 24V DC. Some panels only have 100-240V AC mains, others run on 110V DC control power. The MS3104 covers all of these — AC or DC, including a 12V DC option — so you’re not forced to add a separate power supply just for one signal conditioner. There’s also a fast-response /K option if your loop needs a quicker 10ms response instead of the standard 85ms, useful for fast trip or alarm signals.

Before we quote a signal conditioner like this, we would normally check: the input signal type and range (current or voltage), what output range each downstream device needs on Output 1 and Output 2, the panel’s available power supply (AC or DC, and voltage), whether standard or fast /K response is required, and the DIN-rail space available (it’s a compact 49.8mm wide unit). Send us these details and we can confirm the right variant before you order. Hope this helps.

Input TypesDC current (100µA to 200mA) or DC voltage (200mV to 600V)
Input Options4-20mA, 2-10mA, 1-5mA, 0-20mA, 10-50mA; 0-1V, 0-5V, 0-10V, 1-5V, ±5V, ±10V
Allowable Input30V DC max. (voltage) / 40mA DC max. (current), continuous
Output 1 & 20-20mA current (span 4-20mA) or -10 to 10V voltage (span 10mV-20V)
AccuracyBetter than ±0.1% of span (at 25°C±5°C)
Temperature EffectBetter than ±0.2% of span per 10°C change
Response Time85ms max. (0-90%) standard; 10ms with /K option
CMRR100dB min. (500V AC, 50/60Hz)
Power Supply100-240V AC, 24V DC (±10%), 110V DC, or 12V DC (±20%)
Power Consumption6.5VA (AC), 1.6W (24V DC), 2.5W (110V DC), 1.3W (12V DC)
Isolation5-way isolation between input, output 1, output 2, power, and ground
Insulation Resistance100MΩ min. (@ 500V DC)
Dielectric Strength2000V AC for 1 minute (500V AC between outputs)
Enclosure / MountingABS resin (UL 94V-0), DIN rail mounting, M3.5 screw terminal
DimensionsW49.8 × H102.0 × D40.0 mm
Weight140g max.
Operating Temperature-5 to 55°C, 5-90% RH non-condensing
Storage Temperature-10 to 60°C
StandardsEMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU, Installation Category II

Download MTT MS3104 Terminal Block Type High-Level Signal Conditioner (Isolator) information here

Datasheet: MTT_SpecSheet_MS3104_Rev19_E