MTT MS3103 Terminal Block Type Millivolt Isolator

We had an enquiry from a customer with a load cell on a hopper scale who needed the weight signal to feed both their batching PLC and a separate, independent overload alarm relay, from the same load cell.

This looks simple, but millivolt signals are already the most fragile signal type to wire in a plant, and splitting one output to feed two separate systems multiplies that risk — any loading or ground-sharing between the two destinations shows up as drift or noise on both. The lower the signal level, the less margin there is for error.

For this, we would normally recommend the MTT MS3103, a terminal block type millivolt isolator with isolated dual output. It takes a low millivolt input and splits it into two fully independent, isolated DC outputs, so a control system and a separate alarm or monitor can both read the same measurement without interacting. It accepts a choice of AC or DC power, so it fits panels without a dedicated low-voltage supply, and it converts the signal to something robust right at the source, where the millivolt wiring terminates. It mounts on DIN rail, with front-accessible zero and span trimmers for on-site calibration.

Before we quote, we would normally check the millivolt span from your sensor, the output range needed on each of the two outputs, and the power supply available at the panel. Hope this helps — send us your details and we can confirm the right model.

Input Range-200mV to 200mV, span 5mV to 400mV
Input Resistance1MΩ min.
Allowable Input Voltage30V DC max., continuous
Output 1 & 2Current 0-20mA (span 4-20mA) or voltage -10 to 10V (span 10mV to 20V)
Zero / Span AdjustmentApprox. ±5% of span each
AccuracyBetter than ±0.1% of span (at 25°C±5°C)
Temperature EffectBetter than ±0.2% of span per 10°C change
Response Time160ms max. (0 to 90%)
CMRR100dB min. (500V AC, 50/60Hz)
Power Supply100-240V AC, 24V DC, or 110V DC
Power Consumption6.5VA (AC), 1.6W (24V DC), 2.5W (110V DC)
Isolation5-way isolation between input, output 1, output 2, power, and ground
Dielectric Strength2000V AC for 1 minute
Enclosure / MountingDIN rail mounting, M3.5 screw terminal
DimensionsW49.8 × H102.0 × D40.0 mm
Weight140g max.
Operating Temperature-5 to 55°C, 5-90% RH non-condensing
Storage Temperature-10 to 60°C

Frequently asked questions

What is the MS3103 used for?
It converts a low millivolt signal, such as from a load cell or strain gauge, into two fully independent, isolated DC outputs, so a control system and a separate alarm or monitor can both read the same measurement.

Can the MS3103 be used with AC power instead of 24V DC?
Yes, it accepts 100 to 240V AC, 24V DC, or 110V DC, so it fits panels that don’t have a clean 24V DC bus available.

What’s the difference between the MS3103 and the MS3003?
The MS3003 has a single isolated output and runs on 24V or 12V DC only. The MS3103 adds a second, independently isolated output and accepts AC or DC power, so use the MS3103 when you need to feed two separate systems from one sensor or only have AC power available.

Does the MS3103 need a separate power supply?
Yes, it needs 100 to 240V AC, 24V DC, or 110V DC to operate — it is not loop-powered.

Download MTT MS3103 Terminal Block Type Millivolt Isolator information here

Datasheet: MTT MS3103 Spec Sheet (PDF)

Manual: MTT MS3103 User’s Manual (PDF)