MTT MS3003 Terminal Block Type Millivolt Isolator

We had an enquiry from a customer running a weighing system on their production line. The load cell output was only a few millivolts, and the reading at the control room kept drifting depending on which cable route it took through the plant. They wanted to know if there is a way to clean up the millivolt signal before it reaches the PLC.

This looks simple, but millivolt signals are actually one of the most fragile signal types to wire on an industrial site. At that level, even a small amount of electrical noise from a VSD, a welding set, or just a long cable run can swamp the real signal. Ground loops between the sensor and the control panel add further error on top of that. Converting to a stronger, standard signal as close to the source as possible is far more reliable than trying to fix the reading downstream.

For this, we would normally recommend the MTT MS3003, a terminal block type millivolt isolator. It takes a low millivolt input, down to a 5mV span, and converts it into a standard 4 to 20mA current or DC voltage output, fully isolated between input, output, and power supply. Because it is isolated, it breaks the ground loop and rejects common-mode noise picked up along the cable run. It mounts on DIN rail, so it can sit right in the junction box near the load cell or sensor, and it has field-adjustable zero and span so technicians can calibrate it on site without pulling the unit out of service.

Before we quote, we would normally check the exact millivolt span from the customer’s sensor, the output signal their PLC or DCS expects, and the supply voltage available at the panel, since the MS3003 comes in both 24V DC and 12V DC versions. Hope this helps — feel free to reach out with your site details and we can confirm the right model together.

Input Ranges0-10mV DC, 0-100mV DC, ±10mV DC, ±100mV DC (span 5mV to 400mV)
Input Resistance1MΩ min.
Maximum Input Voltage30V DC max., continuous
Output Signal4-20mA, 0-20mA current; 0-10mV, 0-100mV, 0-1V, 0-10V, 0-5V, 1-5V voltage
Zero / Span AdjustmentApprox. ±2.5% of span each
AccuracyBetter than ±0.1% of span (at 25°C±5°C)
Temperature StabilityBetter than ±0.2% of span per 10°C change
Response Time160ms max. (0 to 90%)
CMRR100dB min. (500V AC, 50/60Hz)
Power Supply24V DC (±10%) or 12V DC (±20%)
Power Consumption40mA max. (24V current out), 70mA max. (12V current out)
Isolation3-way isolation between input, output, and power
Insulation Resistance100MΩ min. (@ 500V DC)
Dielectric Strength1500V AC for 1 minute
Enclosure / MountingABS resin (UL 94V-0), DIN rail mounting, M3.5 screw terminal
DimensionsW25.0 × H94.0 × D40.0 mm
Weight90g max.
Operating Temperature-5 to 55°C, 5-90% RH non-condensing
Storage Temperature-10 to 60°C

Frequently asked questions

What is the MS3003 used for?
It converts low-level millivolt signals, such as those from load cells, strain gauges, or shunt resistors, into a clean, isolated 4 to 20mA or voltage signal that a PLC, DCS, or data logger can read directly.

Can the MS3003 be used with a load cell or strain gauge?
Yes. It accepts millivolt spans as low as 5mV, which covers most load cell and strain gauge outputs, and isolates the signal so ground loops and cable noise don’t affect the reading.

Does the MS3003 need a separate power supply?
Yes, it needs 24V DC or 12V DC to operate — it is not loop-powered. Let us know which supply you have on site so we quote the right version.

Can the MS3003 output a voltage signal instead of 4 to 20mA?
Yes, the output is field-configurable to current or one of several DC voltage ranges, so it can match whatever input your PLC or DCS card accepts.

Download MTT MS3003 Terminal Block Type Millivolt Isolator information here

Datasheet: MTT MS3003 Spec Sheet (PDF)

Manual: MTT MS3000 Series User’s Manual (PDF)

Shopping Cart