Contrec 214Di ATEX Batch Controller

The Contrec 214Di is the ATEX and IECEx certified, intrinsically safe version of the 214D Batch Controller. We get enquiries for this one from customers batching flammable liquids or gases in a hazardous area, where a standard panel meter can’t be installed near the flowmeter without proper certification.

It works with any digital output flowmeter that gives a pulse or frequency signal, so turbine, paddlewheel, and other pulse meters all fit. The controller drives two solid state relay outputs, which is what lets it run a two-stage valve sequence, opening on a coarse flow rate and closing down to a slow trickle near the end of the batch for accuracy, rather than a single on/off valve that overshoots the target. A magnetic key lets you reconfigure the K-factor and settings from outside the enclosure, which matters a lot in a hazardous area since you are not supposed to open the housing while live.

Power comes from a 9-28V DC supply, with battery backup keeping the display and logic running through a power interruption, though the backup does not power the solenoid valves themselves. From our experience, before we quote this one we would check the zone classification of the installation area, the flowmeter’s own hazardous area certificate, and whether the valve wiring and solenoids are separately certified for the zone, since the 214Di certificate only covers the controller itself. Hope this helps.

FunctionIntrinsically safe (ATEX/IECEx) Batch Controller for digital output flowmeters, controlling batch quantities via solid state relay outputs
Input SignalPulse or frequency: sine wave (15mV P-P min), open collector, reed switch, or pulse; 0Hz to 10kHz
K-Factor RangeProgrammable from 0.0001 to 999,999 pulses per unit
Intrinsic Safety ParametersUi = 24V, Ii = 20mA, Pi = 320mW; Cext = 60µF, Lext = 1.5H
Display7-digit 10mm LCD (Batch Total), 5-digit 8.5mm LCD (Preset), Accumulated Total via dedicated key; fully programmable decimal points
Outputs2 x solid state relay outputs, 200mA/30Vdc max, for single or two-stage valve control with 0-9 second programmable delays
Hazardous Area RatingATEX II 2G Ex ia IIB T4 Gb (BVS 15 ATEX E 106 X); IECEx Ex ia IIB T4 Gb (IECEx BVS 15.0099X); CSA Class 1, Group C & D (104840-5)
Power Options9-28V DC (4mA max); 2 x lithium battery packs for display/logic backup (does not power solenoids or sensors)
EnclosureIP67 (NEMA 4X) watertight, polycarbonate and ABS construction
Operating Temperature-20 to +60°C
Dimensions151 x 98 x 26mm (H x W x D)
MountingWall, panel, pipe (51mm), or direct turbine meter mounting
OperationSimple 3-key keyboard; magnetic access strip allows hazardous-area reconfiguration without opening the enclosure; CE compliant

Download Contrec 214Di ATEX Batch Controller information here

Datasheet: Contrec_214D_Batch_Controller

Manual: 214D-M-V7.1_ATEX