| Technical Specifications |
|---|
| ● POWER SECTION |
| Power Requirements | 100 to 240V AC: 85 to 264V AC (47 to 63Hz)
24V DC: 24V DC ±10%
100 to 240V DC: 85 to 264V DC [cite: 1905] |
| Power Supply Sensitivity | Better than ±0.1% of span for each power supply range[cite: 1905]. |
| Power Line Fuse | 160mA fuse is installed as standard[cite: 1905]. |
| Power Consumption | | 100-240V AC | 24V DC | 100-240V DC | | 7.7VA max [cite: 1939] | 2.2W max [cite: 1939] | 2.9W max [cite: 1939] |
|
| ● INPUT SECTION |
| Input Signal | 4 to 20mA DC from 2-wire transmitters[cite: 1916, 1917]. |
| Input Resistance | 250Ω[cite: 1918]. |
| Transmitter Power Supply | Output Voltage: 25V, typical at 0% input | 18V, typical at 100% input[cite: 1920, 1921].
Maximum Drive Current: 25mA, typical[cite: 1922]. |
| Short-Circuit Protection | Limit Current: 26mA, typical[cite: 1923].
Permissible Short-Circuit Duration: Continuous[cite: 1924]. |
| ● OUTPUT SECTION |
| Output Signal Options | 4 to 20mA DC (Standard Code A)[cite: 1896]. |
| Maximum Output Load | 600Ω maximum[cite: 1929].
*Note: Requires 250Ω ±10% for active HART communication loop protocols[cite: 1930, 1931]. |
| Zero Adjustment | Approx. ±5% of span (Adjustable via front-accessible trimmer)[cite: 1932, 1933]. |
| Span Adjustment | Approx. ±5% of span (Adjustable via front-accessible trimmer and internal rotary switch)[cite: 1934, 1935, 1936]. |
| ● HART COMMUNICATION |
| Frequency Bandwidth | 500Hz to 10kHz (with a maximum attenuation limit of -10dB)[cite: 1938]. |
| Transmission Gain | Approx. -3dB (evaluated over a range of 1kHz to 3kHz with a calibrated 250Ω load)[cite: 1938]. |
| Communication Mode | Bidirectional transparent protocol[cite: 1938]. |
| ● PERFORMANCE |
| Accuracy Rating | Better than ±0.1% of span (at 25°C ±5°C)[cite: 1946]. |
| Temperature Effect | Better than ±0.2% of span per 10°C shift in ambient temperature conditions[cite: 1946]. |
| Response Time | 500ms maximum (0 to 90%) matching a step input drive at 100%[cite: 1946]. |
| CMRR | 100dB minimum (evaluated at 500V AC, 50/60Hz)[cite: 1946]. |
| Galvanic Isolation | 4-way isolation configured among input, output, power lines, and ground earth[cite: 1946]. |
| Insulation Resistance | 100MΩ minimum measured under 500V DC across input, output, power, and ground[cite: 1946]. |
| Dielectric Test Ratings | Input / Output / [Power, Ground]: 2000V AC for 1 full minute (Cutoff leakage current: 0.5mA)[cite: 1946].
Power / Ground: 2000V AC for 1 full minute (Cutoff leakage current: 5mA)[cite: 1946]. |
| Surge Withstand Capability | Tested and certified in strict accordance with industrial specification ANSI/IEEE C37.90.1-1989[cite: 1946]. |
| ● PHYSICAL |
| Mounting Configuration | Surface wall mounting or standard heavy industrial DIN rail track installation[cite: 1946]. |
| Wiring Connections | M3.5 terminal screw blocks bundled with drop-out prevention screws and clear power terminal insulation block cover[cite: 1946]. |
| Fastening Torque | 0.8 to 1.0 [Nm] recommended structural assembly torque[cite: 1946]. |
| External Dimensions | W29 × H86 × D125 mm (Total volume inclusive of basic socket base assembly)[cite: 1946]. |
| Net Weight Elements | Main unit module body: 120g max. | Base plug-in socket portion: 80g max.[cite: 1946]. |
| ● MATERIAL |
| Enclosure Shell | ABS resin housing molded to meet UL94V-0 flammability safety class[cite: 1946]. |
| Terminal Blocks | PBT resin structural blocks conforming to UL94V-0 compliance criteria[cite: 1946]. |
| Terminal block Safety Cover | PC resin cover panel structured under UL 94V-2 flame retardancy rules[cite: 1946]. |
| DIN Rail Clip Stopper | PP resin molded compound rated at UL 94HB resistance class[cite: 1946]. |
| Screw Terminals | Industrial-grade high-tensile nickel-plated steel[cite: 1946]. |
| Contact Interfaces | High-grade industrial brass finished with a uniform 0.2µm gold plating finish layer[cite: 1946]. |
| Internal PCB Layers | Woven glass fabric combined with structural epoxy resin core (FR-4: UL 94V-0 certified)[cite: 1946]. |
| Conformal Anti-Humidity Coating | HumiSeal 1A27NS premium polyurethane defensive thin-film protective formulation[cite: 1946]. |
| ● STANDARDS CONFORMITY |
| Operating Environmental Parameters | Ambient Operating Ranges: Temperature envelope: -5 to 55°C | Atmospheric Relative Humidity capacity: 5 to 90% RH (fully non-condensing format)[cite: 1946].
Safe Storage Conditions: Warehouse long-term safe storage temperature rating limits: -10 to 60°C[cite: 1946]. |
| * HumiSeal® is a registered trademark of Chase Corporation[cite: 1963]. |