MTT MS3702B Slim Plug-In RTD Temperature Transmitter

The MTT MS3702B is a slim plug-in RTD temperature transmitter tuned for narrow-span measurement, where a temperature process moves within a tight band and needs to be resolved with more precision than a wide-range transmitter can offer. It reads a Pt or JPt RTD, linearizes the signal, and delivers it as one or two isolated DC outputs, keeping full accuracy even when the measured span is as narrow as 30-50°C.

Like the rest of the plug-in transmitter range, it clips into its own socket base so the unit can be swapped for calibration or replacement in seconds without disturbing the field wiring. Where a dual-output configuration is used, both outputs remain isolated from each other, the input, and the power supply, so one narrow-span RTD reading can feed a control loop and a monitoring or logging system at the same time. Flexible AC or DC power and wall or DIN rail mounting make it straightforward to fit into an existing panel, and standard upscale burnout protection helps flag a broken sensor rather than reporting a misleading reading.

Input TypesPt 100Ω, JPt 100Ω, or Pt 50Ω
Temperature Range-200 to +850°C (Pt 100Ω); -200 to +500°C (JPt 100Ω); -200 to +600°C (Pt 50Ω)
Minimum Input Span30-50°C (Pt 100Ω/JPt 100Ω); 60-100°C (Pt 50Ω)
Excitation CurrentApproximately 1mA for Pt type at 0-100°C
Lead Wire Resistance200Ω maximum per wire
Output0-20mA DC, 4-20mA DC, or DC voltage ranges from 0-10mV up to ±10V (single or isolated dual output)
Isolation4-way isolation between input, Output 1, Output 2, power, and ground
Power Supply100-240V AC (47-63Hz), 24V DC ±10%, or 100-240V DC
AccuracyBetter than ±0.15% of span (at 25°C±5°C)
Temperature EffectBetter than ±1.0% of span per 10°C ambient change
Response Time240ms maximum (0-90%)
CMRRMinimum 100dB
Insulation Resistance100MΩ minimum at 500V DC
Dielectric Strength2000V AC for one minute
Sensor Burnout ProtectionUpscale, standard
Dimensions (W x H x D)29mm x 86mm x 125mm
WeightMain unit up to 120g; socket up to 80g
MountingWall or DIN rail mounting, plug-in socket base
TerminalsM3.5 screw terminals
Operating Temperature-5 to 55°C ambient (storage: -10 to 60°C)
Operating Humidity5-90% RH, non-condensing

Download MTT MS3702B Slim Plug-In RTD Temperature Transmitter information here

Datasheet: MTT_SpecSheet_MS3702B_Rev18_E