MTT MS3002 Terminal Block Type RTD Temperature Transmitter

We had an enquiry from a customer who needed to bring an RTD reading into their PLC, but the raw resistance signal from the sensor wasn’t something the controller’s analog input card could accept directly – and running that resistance signal any distance risked measurement error from the lead wire itself.

This looks simple, but before picking a part number we’d need a few details. Which RTD type are you using – Pt100Ω, JPt100Ω, Pt50Ω, or Ni508.4Ω – and over what temperature range? What output signal does your PLC or DCS accept – 4~20mA, 0~10V, or another range? And do you have 24VDC or 12VDC available on site? The MTT MS3002 covers all four RTD types, but the exact order code depends on your specific sensor type, output, and power combination.

In actual application, the MS3002 is a terminal block type transmitter that mounts on DIN rail right where your RTD wiring terminates, converting the resistance signal into an isolated DC output before lead-wire resistance or electrical noise has a chance to affect the reading (rated for lead wire resistance up to 200Ω per wire). Input, output, and power are all isolated from each other, zero and span are field-adjustable, and response time is 170ms standard, with a 10ms high-speed version available if your process needs a faster reaction. It runs on 24VDC or 12VDC power (the 12VDC version isn’t CE marked).

From our experience, before we quote this, we would normally check your RTD type, the temperature range you’re measuring, your required output signal, your available power supply, and your lead wire length/resistance. Hope this helps.

  • Function: converts RTD input into a commonly used isolated DC signal
  • Input: RTD types Pt100Ω (-200 to +850°C), JPt100Ω (-200 to +500°C), Pt50Ω (-200 to +600°C), Ni508.4Ω (-50 to +250°C)
  • Output: 4~20mA, 0~20mA, 1~5V, 0~5V, 0~10V, 0~10mV, ±10V, ±5V, ±1V, 0~1V, 0~100mV (and other ranges)
  • Excitation current: approx. 1mA
  • Lead wire resistance: 200Ω max per wire
  • Response time: 170ms max standard; high-speed response version 10ms max
  • Power supply: 24V DC or 12V DC (12V DC version excluded from CE marking)
  • Isolation: input, output, and power mutually isolated
  • Field-adjustable zero and span
  • Mounting: terminal block type, DIN rail
  • Standards: CE* (*except 12V DC power version), RoHS

Frequently asked questions

What is the MTT MS3002 used for? It converts a raw RTD (resistance) signal into a standard, isolated DC signal (such as 4~20mA or 0~10V) that a PLC, DCS, or data logger can read directly, while rejecting lead-wire and electrical noise error.

Can the MS3002 be used with any RTD type? It supports Pt100Ω, JPt100Ω, Pt50Ω, and Ni508.4Ω, but the exact input range must be specified at ordering, since it’s not field-switchable.

What’s the difference between the MS3002 and the MS3001? The MS3002 takes an RTD (resistance) input; the MS3001 takes a thermocouple input. They’re not interchangeable, so confirm which sensor type you actually have before ordering.

Does the MS3002 need a separate power supply? Yes, it needs an external 24V DC or 12V DC supply.

Download MTT MS3002 Terminal Block Type RTD Temperature Transmitter information here

Datasheet: MS3002 Spec Sheet (PDF)

Manual: MS3000 Series User’s Manual (PDF)