Build-to-order loop powered process converter - this listing: dual output, both 4~20mA, AC230V auxiliary power.

Category: Signal Conditioners, Signal Isolators

Price on request

Send us your requirement and we'll reply with a quotation and technical advice.

⏱ We reply within 1 working day. Specs & downloads ↓
🛠️
Lifetime technical support
🚚
Free domestic shipping
🎯
Calibration services

Follow Celectric's WhatsApp Channel →

Product details

We had an enquiry from a customer who needed to duplicate an existing 4~20mA loop signal into two separate outputs, powered from AC230V – one signal going to a PLC and another to a local indicator, for example. The ADtek MT-CL is built for exactly this, and this particular listing, MT-CL2-DD-A2, is a specific pre-configured build: dual output, both outputs 4~20mA, with AC230V auxiliary power.

This looks simple, but the MT-CL’s part number actually encodes the full configuration. ADtek builds this 8-pin plug-in converter to order from an order code – output loop (single or dual), output 1 range, output 2 range, and auxiliary power voltage. The “2” means dual output, the two “D”s mean both outputs are 4~20mA, and “A2” means AC230V auxiliary power. If you need a different combination – single output, a voltage range instead of current, or a different auxiliary supply (AC115V, or DC12/24/48/110V) – that would be a different part number entirely.

In actual application, the MT-CL takes a DC 4~20mA input and reprograms it to 6 popular output ranges by dip switch, so it’s commonly used to duplicate or isolate a loop signal at low cost. It plugs into the same 8-pin socket as the rest of ADtek’s MT series, which keeps spares simple.

From our experience, before we quote this, we would normally confirm you need exactly this configuration – dual 4~20mA output on AC230V power – since a different output range or power supply changes the part number. Hope this helps.

This configuration (MT-CL2-DD-A2): dual output (2); Output 1: 4~20mA (D); Output 2: 4~20mA (D); Auxiliary power: AC230V (A2)

Input: DC 4~20mA

Output ranges: 6 popular ranges programmable by dip switch

Order code structure: MT-CL [output loop: 1=single, 2=dual] – [output 1 range][output 2 range] – [aux power: A1=AC115V, A2=AC230V, D12/D24/D48/D11=DC12/24/48/110V]

Mounting: 8-pin plug-in, ADtek MT series panel

Download Adtek MT-CL2-DD-A2 information here Datasheet: https://www.adtek.com.tw/uploads/root/Catalog/datasheet/D/Datasheet-EN/D-02-MT-CL-DataSheet-EN-V10-170103.pdf Manual: not published separately by ADTEK for this model – please contact us if you need installation guidance

Not sure this is the right instrument?

Tell us about your application and our engineers will recommend the right model.