Model: PD8-765-6X3-20 Product Type: Explosion-Proof Process and Temperature Meter Input: Current (4-20 mA), Voltage (0-10 V), Thermocouple, RTD Output Options: 4-20 mA Output Power: 85-265 VAC, 90-265 VDC Approvals: ATEX (FP), CE, CSA (XP), FM (XP), IEC (FP) Transmitter Power: 24 VDC @ 200 mA + 24 VDC @ 40 mA Display Category: LED, Single Line, Sunlight Readable, Large Display Display: 1.2″ High, 4 Digits, Red LED Warranty: 3 years Product Family: PD8-765 Product Category: Explosion-Proof, Field Mounted Indicators Product Application: Level, Pressure, Temperature, Process, Hazardous Area, Pump Control
Wiring Diagram:
General
Display: 1.20” (30.5 mm) red LED, 4 digits (-1999 to 9999) Display Intensity: Eight user selectable intensity levels Programming Methods: Four SafeTouch through-glass buttons when cover is installed. Four internal pushbuttons when cover is removed. Noise Filter: Programmable 2 to 199 (0 will disable filter) Display Update Rate: Process/RTD: 3.7-5/sec; TC: 1.8-2.5/sec Overrange: Display flashes 9999 Underrange: Display flashes -1999 Recalibration: All inputs are calibrated at the factory; recalibration is recommended at least every 12 months. Max/Min Display: Stored until reset by user or meter is turned off. Password: Restricts modification of programmed settings. Non-Volatile Memory: Settings stored for a minimum of 10 years. Power Options: 85-265 VAC, 50/60 Hz; 90-265 VDC, 20 W max or 12-36 VDC; 12-24 VAC, 6 W max. Required Fuse: UL Recognized, 5 A max, slow-blow; up to 6 meters may share one fuse. Normal Mode Rejection: 64 dB at 50/60 Hz Isolation: 4 kV input/output-to-power line; 500 V input-to-output or output-to-24 VDC supplies. -6X5 skus only: 100 V output-to-24 VDC supply Environmental: T6 Class operating temperature range Ta = -40 to 60°C T5 Class operating temperature range Ta = -40 to 65°C Connections: Power & Signal: removable screw terminal blocks accept 12 to 22 AWG. Serial: RJ11 header, standard on all meters. Enclosure: Explosion-proof die cast aluminum with glass window, corrosion resistant epoxy coating, color: blue. NEMA 4X, 7, & 9, IP68. Default conduit connections: Four ¾” NPT threaded conduit openings and two ¾” NPT metal conduit plugs with 12 mm hex key fitting installed. Additional conduit opening configurations may be available; verify quantity and sizes on specific device labeling during installation. Dimensions: 6.42″ x 7.97″ x 8.47″ (W x H x D) (163 mm x 202 mm x 215 mm) Weight: 16.0 lbs (7.26 kg) Warranty: 3 years parts & labor
Process Inputs
Inputs: Field selectable: 0-20 mA, 4-20 mA, 1-5 V, ±10 V Accuracy: ±0.05% FS ±1 count; square root: ±0.1% FS ±2 counts Function: Linear or square root Low-Flow Cutoff: 0 to 9999 (0 disables cutoff function) Decimal Point: Up to 3 decimals: d.ddd, dd.dd, ddd.d, or dddd Calibration: Scale without signal or calibrate with signal source Calibration Range: User programmable over entire range of meter Input Impedance: Voltage range: greater than 1 M Ω, Current Range: 50-100 Ω, varies with resettable fuse impedance Input Overload: Protected by automatically resettable fuse HART Transparency: Analog input will not interfere with existing HART communications on the wired 4-20 mA signal Temperature Drift:
0 to 65°C ambient
-40 to 0°C ambient
Current: ±0.20% FS (50 PPM/°C)
Current: ±0.80% FS
Voltage: ±0.02% FS (1.7 PPM/°C)
Voltage: ±0.06% FS
Transmitter Supply: Isolated, one or two transmitter supplies P1: 24 VDC ±10% @ 200 mA max (-1 option) P1 & P2: 24 VDC ±10% @ 200 mA & 40 mA max (-2 option)
Temperature Inputs
Inputs: Factory calibrated, field selectable: type J, K, T, or E thermocouples and 100 Ω platinum RTD (0.00385 or 0.00392 curve) Resolution: 1°; type T: 1° or 0.1° Cold Junction Reference: Automatic Temperature Drift: ±2°C maximum Offset Adjustment: Programmable to ±19.9°. This parameter allows the user to apply an offset value to the temperature being displayed. Input Impedance: Greater than 100 k Ω Sensor Break: All relays and alarm status LEDs go to alarm state.
Input Type
Range
Accuracy (0-65° C)
Accuracy (-40-0° C)
Type J
-58° to 1382° F -50° to 750° C
±2° F ±1° C
±5° F ±3° C
Type K
-58° to 2300° F -50° to 1260° C
±2° F ±1° C
±4° F ±2° C
Type T
-292° to 700° F -180° to 371° C
±2° F ±1° C
±13° F ±7° C
Type T 0.1° Res
-199.9° to 700.0° F -180.0° to 371.0° C
±1.8° F ±1° C
±13° F ±7.2° C
Type E
-58° to 1578° F -50° to 870° C
±2° F ±1° C
±11° F ±6° C
100 Ω RTD
-328° to 1382° F -200° to 750° C
±1°F ±1° C
±5°F ±3° C
Relays
Rating: 2 Form C (SPDT); rated 3 A @ 30 VDC or 3 A @ 250 VAC resistive load; 1/14 HP @ 125/250 VAC inductive loads Deadband: 0-100% FS, user selectable High or Low Alarm: User may program any alarm for high or low Relay Operation:
Automatic (non-latching)
Latching
Pump alternation control
Relay Reset: User selectable via front panel buttons or PC
Automatic reset only (non-latching)
Automatic plus manual reset at any time (non-latching)
Manual reset only, at any time (latching)
Manual reset only after alarm condition has cleared (latching).
Automatic Reset: Relays reset when input passes the reset point Manual Reset: Front panel button, MeterView, Modbus registers Time Delay: 0 to 199 seconds, on and off delays; programmable Fail-Safe Operation: Programmable, independent for each relay. Relay coils are energized in non-alarm condition. In case of power failure; relays will go to alarm state. Auto Initialization: When power is applied to the meter, relays will reflect the state of the input to the meter.
Isolated 4-20 mA Transmitter Output
Scaling Range: 1.00 to 23.00 mA; reverse scaling allowed. Calibration: Factory calibrated 4.00 to 20.00 mA Accuracy: ±0.1% FS ±0.004 mA Temperature Drift: 50 PPM/°C Note: Analog output drift is separate from input drift Isolation: 500 V input-to-output or output-to-24 VDC supplies; 4 kV output-to-power line External Power: 35 VDC maximum Output Loop Resistance:
Loop Resistance
Power Supply
Minimum
Maximum
24 VDC
10 Ω
700 Ω
35 VDC (external)
100 Ω
1200 Ω
Serial Communications
Compatability: EIA-485 Connectors: Removable screw terminal connector Max Distance: 3,937′ (1,200 m) max Status Indication:Separate LEDs for Power (P), Transmit (TX), and Receive (RX) Protocol: Two selectable. PDC protocol (for use with MeterView) and Modbus RTU Meter Address: PDC protocol: 0 to 99, Modbus protocol: 1 to 247 Baud Rate: 300 to 19,200 bps Transmit Time Delay: Programmable 0 to 199 ms or transmitter always on for RS-422 communications. Data: 8 bit (1 start bit, 1 stop bit) Parity: None (2 stop bits), even, or odd (Modbus only; PDC protocol does not use parity) Byte-to-Byte Timeout: 0.01 to 2.54 seconds (Modbus only) Turn Around Delay: Less than 2 ms (fixed) Note: Both downloadable protocol register tables can be found in the documentation list below.
External Switch Contacts
Open State: +5 VDC open contact on switch input terminals Closed State: Closed contact switch input terminal to common/ground, active low 0 to 0.4 VDC, or open collector transistor activated input
Product Ratings and Approvals
FM Enclosure: Type 4X; IP66 Class I, Division 1, Groups B, C, D Class II, Division 1, Groups E, F, G Class III, Division 1, T5/T6 Class I, Zone 1, AEx d, IIC Gb T5/T6 Zone 21, AEx tb IIIC T90°C; Ta -40°C to +65°C T6 Ta = -40°C to +60°C; T5 Ta = -40°C to +65°C Certificate Number: 3047283 CSA: Class I, Division 1, Groups B, C, D Class II, Division 1, Groups E, F, G Class III, Division 1 Class I Zone 1 Ex d IIC Zone 21 Ex tb IIIC T90°C -40°C < Tamb. < +60° C; Temperature Code T6 -40°C < Tamb. < +65° C; Temperature Code T5 Enclosure Type 4X & IP66 Certificate Number: 2531731 ATEX: II 2 G D Ex d IIC T* Gb Ex tb IIIC T90°C Db IP68 Ta = -40°C to +*°C *T6 = -40°C to +60°C *T5 = -40°C to +65°C Certificate number: Sira 12ATEX1182 IECEx: Ex d IIC T* Gb Ex tb IIIC T90°C Db IP68 Ta = -40°C to +*°C *T6 = -40°C to +60°C *T5 = -40°C to +65°C Certificate Number: IECEx SIR 12.0073
MeterView® for Trident
MeterView software allows remote programming and data acquisition of the Trident series. The remote programming allows for all available meter settings to be programmed from a personal computer through an easy user-friendly interface. The data acquisition allows the user to gather readings from up to 100 meters at user-selected intervals and generate charts using common tools like Microsoft® Excel.
Digital Panel Meters make a great front end to a PC-based data acquisition system. They are easy to set up, can be used for a wide range of inputs, will power the transmitter, and best of all provide a local display of the process. Precision Digital has the perfect package with its Trident Digital Panel Meters, a wide selection of serial adapters and converters and free MeterView software. Data is displayed on the PC and written to a file that could then be imported into a spreadsheet or other application.
Data Logging up to 100 Trident Meters
Sample File Generated by MeterView®
Great for tank level monitoring!
Ordering Example: System consisting of 10 Tridents & MeterView