Specifications
Except where noted all specifications apply to operation at +25°C.
Input
Input: 4-20 mA
Accuracy: ±0.02% of span ±1 count, Square root and programmable exponent: 10-100% FS
Voltage Drop: Without backlight: 1.5 V maximum,
With backlight: 4.7 V maximum
Equivalent Resistance: With backlight off: 75 Ω @ 20 mA
With backlight on: 225 Ω @ 20 mA
Input Overload: Over current protection to 1 A maximum
Temperature Drift: 25 PPM/°C from -40 to 75°C ambient
Function: Linear, square root, or programmable exponent
Low-Flow Cutoff: 0.0 to 999,999.9
HART Transparency: Analog input will not interfere with existing HART communications on the wired 4-20 mA signal
Display
Display: Dual-line LCD with backlight. Both lines 14-segment alphanumeric. Top: 0.7″ (17.8 mm), Bottom: 0.4″ (10.2 mm). Display may be programmed to turn red and flash a user-defined message on alarm condition.
Backlight: Powered by 4-20 mA loop. Intensity varies with signal level
PD6622 & PD6626:
Top line: 5 digits (-9999 to 99999) or 5 characters (all capital & most lower case letters)
Bottom line: 8 digits (-9,999,999 to 99,999,999; separated by commas) or 8 characters (all capital & most lower case letters)
PD6624 & PD6628:
Top line: 5 digits (-9999 to 99999) or 5 characters (all capital & most lower case letters)
Bottom line: 8 digits (-9,999,999 to 99,999,999; separated by commas) or 8 characters (all capital & most lower case letters)
Bargraph: 20 segments, numeric percent indication at top
Decimal Point & Commas
Top line: Up to four decimal places
Bottom line: Up to seven decimal places and commas to indicate 1000s (i.e. 88,987,628)
Dual-Scale Feature: The input can be displayed in different scales on the top and bottom lines. For instance, the top line could display the flow in GPM and the bottom line could display that same input in CFM.
Alarm Indication: Red backlight, flashing display, alarm symbol (!); Symbols are not available on bargraph skus.
Alarm Message: On or Off; user programmable, 8 characters maximum. Displayed every 10 seconds for 1 second on bottom line.
Display Update Rate: Ambient > -10°C: 1 update/second
Ambient -20°C: 1 update/2 seconds
From -20°C to -40°C the update rate slows down 1 second for every -2°C (e.g. at -24°C, 1 update/4 seconds).
Overrange: Top: 99999; Bottom: 99,999,999 (flashing)
Underrange: Top: -9999; Bottom: -9,999,999 (flashing)
General
Environmental: Operating temperature range:
-40 to 75°C for safe area products
-40 to 70°C for hazardous area products
Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing. Printed circuit boards are conformally coated.
Programming Method: Front panel & Free PC-based USB programming software
Enclosure & Materials: Enclosure: 1/8 DIN, IP65, NEMA 4X front panel, high impact plastic, NORYL® polyphenylene ether & polystyrene blend (PPE PS) resin, UL 94V-0, Color: gray, Gasket: silicone rubber, Faceplate: LEXAN® polycarbonate (PC) film, Buttons: silicone rubber
Noise Filter: Averages the input signal over a period of time between 1 and 16 seconds to dampen the effects of a noisy signal that causes a jumpy display.
Recalibration: Recalibration is recommended at least every 12 months.
Max/Min Display: Max/min readings reached by the process are stored until reset by the user or until power to the meter is turned off.
Password: There are three password types available: Main, Total, and Grand Total. The Main password prevents access to the meter Programming Mode. Total and Grand Total passwords prevent resetting the total and grand total, respectively.
Non-Volatile Memory: All programmed settings and total and grand total values are stored in non-volatile memory for a minimum of ten years if power is lost.
Normal Mode Rejection: 64 dB at 50/60 Hz
Connections: Removable screw terminals accept 12 to 22 AWG.
DI Digital Input Contacts: 2.1 VDC on contact. Connect normally open contacts across DI+ and DI
DI Digital Input Logic Levels: Logic High: 2.4 to 30 VDC (max)
Logic Low: 0 to 0.9 VDC
Tightening Torque: Screw terminal connectors: 4.5 lb-in (0.5 Nm)
Mounting screws: 8.0 lb-in max. (0.9 Nm)
Overall Dimensions: 4.68″x 2.45″x 3.79″ (119 mm x 62 mm x 96 mm) (W x H x D)
Weight: 8.7 oz (247g) with option board
Warranty: 3 years parts and labor
Rate/Totalizer
Rate Display Capability: Top display: -9999 to 99999; bottom display: -9,999,999 to 99,999,999 (with commas)
Total Display Capability: Top display: -9999 to 99999; bottom display -9,999,999 to 99,999,999 (with commas)
Grand Total Display Capability: Top display: N/A; bottom display -9,999,999 to 99,999,999 (with commas)
13-Digit Total & Grand Total Capability: Up to 9,999,999,999,999 using both lines with 13-digit total feature enabled.
Total & Grand Total Indication: On bottom display; “T” indicates total and “GT” indicates grand total. (not available on bargraph skus)
Total Decimal Point: Up to four decimal places on top, up to seven decimal places on bottom. Total decimal point is independent of rate decimal point.
Totalizer: Calculates total based on rate and rate units to display total in engineering units. A custom factor must be programmed if using custom defined units.
Time Base: Seconds, Minutes, Hours, Days
Totalizer Rollover: Totalizer rolls over when display exceeds 99,999,999 (9,999,999,999,999 if 13-digit limit enabled). Relay status reflects display.
Total & Grand Total Reset: Via front panel button or external contact closure on digital input
Total & Grand Total Reset Passwords: Total and grand total passwords may be entered to prevent resetting the total or grand total unless a password is entered.
Non-Resettable Grand Total: Grand total reset may be disabled through the meter interface. Grand total reset may be permanently disabled by selecting YES at the PERMLOCK menu.
Caution: Once the Grand Total has been programmed as “non-resettable” the feature cannot be disabled
Common Open Collector & Relay (Alarm) Specifications
High or Low Alarm: User programmable for high or low alarm
Alarm Deadband: 0-100% FS, user programmable
On & Off Time Delay: 0 to 9,999 seconds
Fail-Safe Operation: Independent for each open collector and relay
Alarm Operation: Automatic, Automatic with manual override, Latching (manual reset anytime), Latching with reset after cleared (manual reset only after alarm has cleared)
Alarm Indication: Red backlight, flashing display, alarm symbol (!) (symbols not available on bargraph skus)
Alarm Message: On or Off; User programmable, 8 characters maximum. Displayed every 10 seconds for 1 second on bottom line
Alarm Acknowledge: Front panel ACK button or external digital input resets output and screen indication
Auto Initialization: When power is applied to the meter, open collectors and relays will reflect the state of the input to the meter.
Timer Output: One-shot or Continuous
Off Time Delay: 1 sec to 99:59:59 (hrs:min:sec)
On Time: 1 sec to 99:59:59 (hrs:min:sec)
Stopwatch: Output turns on when started and off when stopped
Open Collector Outputs
Rating: Two NPN, Isolated open collector, 30 VDC @ 150 mA max
Output Assignment: Pulse, Alarm, Timer, Total Reset, Stopwatch on/off, or Disable
Pulse Output Source: Rate, Total, Grand Total, or Test Frequency
Pulse Output Factor: 0.000001 to 999,999.9
Pulse Width: 0.5 ms @ 1 kHz; 500 ms @ 1 Hz; 50% duty cycle
Pulse Output Frequency: 1,000 Hz maximum
Quadrature Pulse Output: Available for Output 2 (90° behind Output 1)
Alarm Output Source: Assign to Rate, Total, Grand Total or Digital Input
Solid State Relays
Rating: Resistive Load: 250 VAC/DC @ 1 A
Inductive Load: 75 VA @ 0.6 A, 250 VAC/DC max (Safe Area only)
Noise Suppression: Metal oxide varistors across outputs
Relay Assignment: Alarm, Sample, Timer, Batch, Stopwatch on/off, or Disable
Alarm Output Source: Assign to Rate, Total, Grand Total, or Digital Input
4-20 mA Transmitter Output
Accuracy: ±0.05% FS ±0.001mA
Output Source: Rate, total, re-transmit; reverse scaling allowed
Scaling Range: 1.00 to 23.0 mA
Disable: High impedance state, less than 1 mA
Calibration: Factory calibrated 4.00 to 20.00 mA
Underrange: 1.0 mA, 3.5 mA, or 3.8 mA (If input < 3.5 mA), or Off; user selectable
Overrange: 20.5 mA, 20.8 mA, or 23.0 mA (If input > 20.5 mA), or Off; user selectable
Isolation: 500 V input-to-output
Temperature Drift: 0.5 μA/°C max from -40 to 75°C ambient
External Loop Power Supply: 7.0 VDC to 30.0 VDC maximum
Output Loop Resistance: 10-750 Ω @ 24 VDC; 100-1100 Ω @ 30 VDC
Batch Control
Methods: Automatic or Manual, count up or count down
Manual Batch Start: Pressing F1 function key starts the batch
Manual Batch Pause/Stop: Pressing F3 once pauses the batch, pressing it twice cancels the batch
Automatic Batching: The Loop Leader can be used as an automatic batch controller where batches run continuously without operator input.
Batching Relay Operation: Single or dual-relay batching with optional preclose for dual-stage operation
Batch Preset: Set via F2 function key anywhere between 0.0001 to 99,999 based on batch total decimal point. If batch total is assigned to bottom, the preset can be up to 8 digits.
Batch Preclose: For two-stage batch application, a preclose value can be set to close the main flow line.
Automatic Batch Restart Delay: 1 to 9,999 seconds. The batch will automatically restart after completion of the last batch.